For reviewing DC battery servicing scenarios where potential arc locations and current paths may be uncertain.
iPhone: Open this page in Safari, tap Share, then Add to Home Screen. Use the name DC Calculator and tap Add.
Android: Open this page in Chrome, tap the browser menu, then Add to Home screen or Install app, if offered. Use the name DC Calculator.
On a computer? Open this page on your phone to save the shortcut.
System inputs
Estimated results
Calculation method and scope
This calculator reproduces ElecTrain’s workbook formulas using maximum power theory. It represents one DC incident energy method and does not model a specific electrode configuration or compare all available DC methods.
Bolted fault current = voltage ÷ total resistance. Estimated arcing current = half of bolted fault current. Incident energy = 0.01 × location factor × voltage × arcing current × duration ÷ distance², with distance in centimeters.
The location factors follow the workbook: 1× for open air; 2× against a flat surface allowing 180° expansion; 3× inside an enclosure with energy directed outward. Their source and applicability are under review.
Review version on the redesign site. Matching the workbook does not establish applicability to a particular battery system or servicing task.